Rockwell-automation Logix5000 Program Parameters Programming Manual Manual do Utilizador Página 30

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 36
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 29
Chapter 1 Connecting program parameters
Safety program to standard program connection rules
The following table summarizes the rules for using program parameters to connect
a safety program to a standard program.
Tip:
The connection rules for programs also apply to Equipment Phases.
Program_A
(Safety)
Program_B
(Standard)
Input Output InOut Public
Controller Scope
Tag (Safety Class)
Input
Yes Yes Yes
Output
InOut
Public
Controller Scope
Tag (Safety Class)
Yes Yes Yes Alias Alias
An Input parameter from Program_A can connect to an Output parameter
of Program_A (wrap around).
Safety mapping must be used to connect standard class tags to safety class
tags/parameters.
Standard class tags cannot alias safety class tags.
30 Rockwell Automation Publication 1756-PM021A-EN-P - October 2014
Vista de página 29
1 2 ... 25 26 27 28 29 30 31 32 33 34 35 36

Comentários a estes Manuais

Sem comentários