Rockwell-automation Logix5000 Program Parameters Programming Manual Manual do Utilizador Página 27

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 36
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 26
Connecting program parameters Chapter 1
Special considerations apply when using program parameters within safety
programs.
General rules for connecting parameters for safety programs
The following are general rules when connecting parameters for safety programs.
A safety parameter cannot connect to a standard parameter or controller
scoped tag of standard class; the controller scope must be of class safety.
A safety parameter can source a standard parameter, as shown in the
following image.
Safety Output parameters cannot connect to a standard class InOut
parameter.
Safety local tags can alias safety class controller scope tags.
Safety Public parameters can alias safety class controller scope tags.
Safety program parameters
Rockwell Automation Publication 1756-PM021A-EN-P - October 2014 27
Vista de página 26
1 2 ... 22 23 24 25 26 27 28 29 30 31 32 ... 35 36

Comentários a estes Manuais

Sem comentários