Document: 553633
ICSTT-RM405f-EN-P
Issue 07
9-29
2) Select the Slave link associated with the master object.
The editor for the slave link opens
3) Select the General tab.
4) Check that the Ping Mode is set to Read Holding Register.
5) Ensure that a Ping Address has been entered.
6) Check that the Ping Interval is suitable for your application.
Do Not Ping Ping Mode Setting
1) Select the Equipment tab on the Project tree and then a Modbus master object
that has been set up to run the TCP protocol.
Check this by selecting the General tab and that the Protocol row is set to
TCP.