Rockwell-automation AADvance Controller Configuration Guide Manual do Utilizador Página 140

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 286
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 139
5-42
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
Configuration Guide (AADvance Controller)
<tagname>.CF
BOOL
Channel fault
TRUE: module diagnostics detect a fault in the
channel electronics or firmware (state = 7)
<tagname>.V
UINT
Voltage
Reports the channel voltage at the output
terminals, in units of millivolts and with an
accuracy of ± 500mV (††)
<tagname>.I
INT
Current
Reports the current for the channel in milliamps
and with an accuracy of ± 2mA and ± 10% of
measurement
<tagname>.STA
USINT
Channel state
Reports a state value for the channel:
1 = no vfield
2 = de-energized
3 = no load
4 = energized
5 = short-circuit
6 = field fault
7 = faulted
Note: (†) Discrepancy can only be reported TRUE when two modules are active in a
group. (††) The voltage element cannot report values below 0mV.
Vista de página 139
1 2 ... 135 136 137 138 139 140 141 142 143 144 145 ... 285 286

Comentários a estes Manuais

Sem comentários