Rockwell-automation 9301 Series RSView32 Users Guide Manual do Utilizador Página 160

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 769
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 159
6–34 RSView32 User’s Guide
To configure alarm severity:
1. In the Alarm Setup editor, click the Severities tab.
2. Select an alarm severity or an incident.
3. Specify the logging destination. You can log to the alarm log file, to
a printer, or to both. Alarm severities and incidents are logged as
follows:
Alarm What is logged
Severity 1 through 8 In Alarm messages are logged
Out of Alarm Out of Alarm messages are logged for any
severity that has been set up to log In Alarm
messages
Acknowledged Acknowledged messages are logged for any
severity that has been set up to log In Alarm
messages
Fault All Fault messages are logged
Suppression All Suppression messages are logged
Alarm Severities
Alarm Incidents
Alarm Severities
Alarm Incidents
Vista de página 159
1 2 ... 155 156 157 158 159 160 161 162 163 164 165 ... 768 769

Comentários a estes Manuais

Sem comentários