AĆ3
Appendix A
(Continued)
Linear Performance (14 bits)
The following table details guaranteed accuracy and repeatability as compared to
National Bureau of Standards measurements using primary voltage standards. All
sources of error have been included. The following conditions apply:
1. Measurement is within 30 days of calibration.
2. Ambient temperature is 0Ć60 degrees C, draftĆfree and steady.
3. Common mode voltage = 0.
Range Resolution Absolute Accuracy
+
12.50 mvolts 0.76 volts +6 volts
+
25.00 mvolts 1.53 volts +8 volts
+
50.00 mvolts 3.05 volts +12 volts
+
100.00 mvolts 6.10 volts +24 volts
+
1.25 volts 76.25 volts +300 volts
+
2.50 volts 152.5 volts +600 volts
+
5.00 volts 305. volts +1200 volts
+
10.00 volts 610. volts +2400 volts