In configuring the channel input, you define the type of signal that will
be converted on a particular channel. If an input channel is not
defined, the channel is considered to be unassigned and no A/D
conversion will be performed. Refer to table 4.2 for a complete list of
signals that the module will accept.
Table 4.2Ć Channel Signal Configuration
1
Channel
Configuration
Code
Analog
Input
Conversion
Precision
Conversion
Time (max)
2
3
4
5
6
7
8
11
12
13
14
15
16
17
18
21
22
23
24
25
26
1
2
1
2
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
TC Type B
TC Type E
TC Type J
TC Type K
TC Type R
TC Type T
14 bit
14 bit
14 bit
14 bit
14 bit
14 bit
14 bit
14 bit
12 bit
12 bit
12 bit
12 bit
12 bit
12 bit
12 bit
12 bit
14 bit
14 bit
14 bit
14 bit
14 bit
14 bit
75 msec
75 msec
75 msec
75 msec
75 msec
75 msec
75 msec
75 msec
45 msec
45 msec
45 msec
45 msec
45 msec
45 msec
45 msec
45 msec
110 msec
110 msec
110 msec
110 msec
110 msec
110 msec
10.000 V
ă5.000 V
ă2.500 V
ă1.250 V
100.0 mV
ă50.0 mV
ă25.0 mV
ă12.5 mV
10.000 V
ă5.000 V
ă2.500 V
ă1.250 V
100.0 mV
ă50.0 mV
ă25.0 mV
ă12.5 mV
Used with RTD inputs
Used with RTD inputs with 0Ć200 Degree F range.