Rockwell Automation Publication 193-UM011A-EN-P - September 2010 45
Protective Trip and Warning Functions Chapter 3
Bit 0 of Parameter 21, Device Status, will go to “1”
The Trip Relay contact will open
The outputs will be placed in their Protection Fault State (if so
programmed)
Comm Idle Warning
The EC4 Current Monitoring Relay will indicate a Comm Idle warning if:
No warning currently exists
Comm Idle Warning is enabled
The network controller that is communicating to the EC4 Current
Monitoring Relay is placed in idle mode
When the Comm Idle warning conditions are satisfied, the following will occur:
The TRIP/WARN LED will flash an amber 11-blink pattern
Bit 10 in Parameter 15, Wa r n i n g S t a t u s , will go to “1”
Bit 1 in Parameter 21, Device Status, will go to “1”
If a communication idle occurs and either Comm Idle Trip is not enabled or the
Pr FltState parameters are set to “Ignore”, the following will occur:
The outputs will be placed in their Comm Idle State
Remote Trip
The Remote Trip function provided in series B and later devices allows the
capability of tripping the EC4 Current Monitoring Relay from a remote source
(for example, a vibration switch). Proper set-up requires that Remote Trip is
enabled in Parameter 24, Trip Enable, and that an input assignment (Parameters
83 – 86) is configured for Remote Trip.
When the remote trip condition sensor contact closes:
The TRIP/WARN LED will flash a red 15-blink pattern
Bit 14 in Parameter 14, Trip Status, will go to “1”.
The Trip relay contact will open.
IMPORTANT
The Protection Fault state of OUT A and OUT B is defined by Parameter
65 (OUTA Pr FltState), Parameter 66 (OUTA Pr FltValue), Parameter 71
(OUTB Pr FltState), and Parameter 72 (OUTB Pr FltValue).
IMPORTANT
The Comm Idle State of OUT A and OUT B is defined by Parameter 69
(OUTA Dn IdlState), Parameter 70 (OUTA Dn IdlValue), Parameter 75
(OUTB Dn IdlState), and Parameter 76 (OUTB Dn IdlValue).