Rockwell-automation 193-EC4 EC4 Current Monitoring Relay User Manual Manual do Utilizador Página 34

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 33
Rockwell Automation Publication 193-UM011A-EN-P - September 2010 35
Installation and Wiring Chapter 2
External/Remote Reset (FRN 3.001 and later)
To reset a trip from an external/remote location, configure one of the EC4
Current Monitoring Relays inputs for trip reset operation using one of
parameters 83…86. Wire the input as shown in Figure 23 .
Figure 23 - External/Remote Reset Wiring
IMPORTANT
Reset operation is edge sensitive and trip free; that is, holding the
push button down (maintaining the reset contact in a closed position)
will not prevent the EC4 Current Monitoring Relay from tripping.
Reset
1- 5
Vista de página 33
1 2 ... 29 30 31 32 33 34 35 36 37 38 39 ... 156 157

Comentários a estes Manuais

Sem comentários