34 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
Publication
1797-5.5 - September 2011
HART Input Data Descriptions
CHn: HART Communication Status 0: HART CMD3
Communication Disabled or
No Error
1: HART CMD3
Communication
Error between
Adapter & Module
CHn: HART Comm Status (HART CMD3
Response first status byte):
Refer to User Manual
CHn: HART Field Device Status (HART
CMD3 Response second status byte):
Refer to User Manual
Chn: HART Loop Status:
Bit 0: HART enable
Bit 1: Device Connected
Bit 2: Response Error
Bit 3: CMD 48 Update
Bit 4: HART Loop Tolerance Error
Bit 5: HART Update
Bit 6: HART message
Bit 7:
0: Disabled
0: Not Connected
0: No HART message
failure
0: CMD 48 not
updated
0: No HART Current
Fault
0: HART Device
information not
updated
0: No new message
1: Enabled
1: Connected
1: Response ended in error
1: CMD 48 updated
1:HART Current Fault
1: HART Device information
updated since last read
1: HART user message
queue has completed a
message
Reserved
Where PVA = The primary variable for this channel has been acquired.
SVA = The secondary variable for this channel has been acquired.
TVA = The tertiary variable for this channel has been acquired.
FVA = The fourth (quaternary) variable for this channel has been acquired.
Vista de página 33