26 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
Publication
1797-5.5 - September 2011
Byte Order Configuration
Byte Order
Group B
Byte Order
Group A
Description
(1)
Bit 9 Bit 8 Bit 1 Bit 0
0 0 0 0 Little Endian Format (Default) = All data entries in true Little
Endian format.
1 0 1 0 Word Swap = Word swap only values requiring more then one
word,
for example: 32 bit float values.
0 1 0 1 Byte Swap (reserved for future implementation) = Byte swap all
words in data table.
1 1 1 1 Big Endian Format (reserved for future implementation) = All data
entries in true Big Endian format.
(1)
All other combinations are invalid. Values will Revert to the last valid configuration (in case of original
start-up this would be default configuration) and set module Diagnostic Status to "2" configuration
failure.
Digital Filter
Digital Filter
frequency
Decimal
Value
Bits Digital Filter
frequency
Decimal
Value
Bits
2 1 0 2 1 0
10 9 8 10 9 8
0.5 Hz 7 0 0 0 10 Hz 3 1 0 0
1 Hz 6 0 0 1
Not applicable
(1)
2 1 0 1
2 Hz 5 0 1 0 Not applicable 1 1 1 0
4 Hz 4 0 1 1 Not applicable 0 1 1 1
(1)
Decimal Values 2, 1 and 0 are not applicable. Values will Revert to the last valid configuration (in case
of original start-up this would be default configuration) and set module Diagnostic Status to "2"
configuration failure.