ControlNet-to-DeviceNet Linking Device 27
Publication
1788-IN052D-EN-P - February 2007
Green, steady One or more devices
connected and
communicating.
None needed.
Red, flashing One or more connections
timed-out.
Use programming software to view
tags specific to the devices in order
to troubleshoot the DeviceNet
network.
See DeviceNet Modules in
Logix5000 Control Systems,
publication DNET-UM004, for more
information about using controller
tags to troubleshoot connection
errors.
Red, steady Communication error (bus
off condition).
A. Verify that each device has be
assigned a unique node
address.
B. Verify that specified DeviceNet
baud rates are the same.
C. Cycle power to the CN2DN
device.
See DeviceNet Modules in
Logix5000 Control Systems,
publication DNET-UM004, for more
information about using controller
tags to troubleshoot connection
errors.
DNet Network Status Indicator
LED Indicator DeviceNet Network
Status
Recommended Action