3/&5HOD\&DUWULGJH 
Specifications
Backplane Current 0.200A @ +5Vdc
Number of Outputs 1 (N.O. Contact)
Contact Rating
120Vac 50/60Hz @ 0.500A Pilot Duty
minimum 100,000 mechanical switching
cycles
Wiring
12-22 AWG Category 1
1
, use minimum 75°
C copper wiring
Weight
70 g
2.0 oz.
Environment
Operating
Temperature
0° to 60° C (32° to 140° F)
Storage
Temperature
-40° to 85° C (-40° to 185° F)
Relative
Humidity
5 to 95% (without condensation)
Shock Testing
Operating 15 g peak acceleration at 11 ms duration
Non-operating 25 g peak acceleration at 11 ms duration
Vibration Testing 2 g peak acceleration at 10-500 Hz
Agency Certification
(when product or packaging is
marked)
&6$FHUWLILHG3URFHVV&RQWURO(TXLSPHQW
&6$&ODVV,'LYLVLRQ*URXSV$%&'
8/OLVWHG,QGXVWULDO&RQWURO(TXLSPHQW
&(PDUNHGIRUDOODSSOLFDEOHGLUHFWLYHV
$XVWUDOLDQ&7LFN
1 Use this conductor category infomation for planning conductor routing as described in publication
1770-4.1,
Industrial Automation Wiring and Grounding Guidelines
.