Connection Diagram for the RTD Input Module (1771-IR/C)
Field Wiring Arm
Cat. No. 1771-WF
18
17
16
1
15
14
13
12
11
10
9
8
7
6
5
4
3
2
11846-I
RTD
Ground
Chassis
(Channel 1 shown)
RTD Input Module 5
Publication
1771-5.50 – October 1996
Connect your I/O devices to the field wiring arm (cat. no. 1771-WF)
shipped with the module.
!
ATTENTION: Remove power from the 1771 I/O
chassis backplane and field wiring arm before
removing or installing an I/O module.
• Failure to remove power from the backplane or
wiring arm could cause module damage, degradation
of performance, or injury.
• Failure to remove power from the backplane could
cause injury or equipment damage due to possible
unexpected operation.
Channel Terminal
Identification
1 18 C
17 B
16 A
2 15 C
14 B
13 A
3 12 C
11 B
10 A
4 9 C
8 B
7 A
5 6 C
5 B
4 A
6 3 C
2 B
1 A
Connect Wiring to the
Field Wiring Arm