Rockwell-automation 1756-Lx_Mx ControlLogix Controller and Memory Boar Manual do Utilizador Página 36

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 52
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 35
36 ControlLogix® Controller and Memory Board
Publication
1756-IN101J-EN-P - November 2004
OK Indicator
Color Description Recommended Action
off No power is applied. When ready, turn on power
to the controller.
flashing
red
If the controller is: Then:
a new controller
(just
out of the box)
The controller requires a
firmware update.
See “Update the
Controller” on page 29.
NOT a new
controller
(previously in
operation)
Major fault occurred. See “Clear a Major Fault
on page 37.
solid red The controller detected a non-recoverable fault,
so it cleared the project from memory.
See “Clear a
Non-Recoverable Fault” on
page 38.
solid
green
The controller is OK None
flashing
green
The controller is storing or loading a project to or
from nonvolatile memory.
If the controller has a
CompactFlash card, leave
the card in the controller
until the OK LED turns solid
green.
Vista de página 35
1 2 ... 31 32 33 34 35 36 37 38 39 40 41 ... 51 52

Comentários a estes Manuais

Sem comentários