Rockwell-automation 1756-Lx_Mx ControlLogix Controller and Memory Boar Manual do Utilizador Página 33

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 52
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 32
ControlLogix® Controller and Memory Board 33
Publication
1756-IN101J-EN-P - November 2004
Interpret Controller LEDs
RUN Indicator
I/O Indicator
Color Description Recommended Action
off The controller is in Program or Test
mode.
See “Choose the Operating
Mode of the Controller” on
page 39.
solid green The controller is in Run mode.
Color Description Recommended Action
off Either:
There are no devices in the I/O
configuration of the controller.
Add the required devices to
the I/O configuration of the
controller.
The controller does not contain a
project (controller memory is empty).
Download the project to the
controller.
solid green The controller is communicating with
all the devices in its I/O configuration.
None
flashing
green
One or more devices in the I/O
configuration of the controller are not
responding.
Go online with RSLogix 5000
software and check the I/O
configuration of the controller.
flashing red The chassis is bad. Replace the chassis.
Vista de página 32