Rockwell-automation 1746-HSTP1 Stepper Controller Module/ User Manual Manual do Utilizador Página 39

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 38
Publication 999-121 - December 1999
5-4
Configuration and Programming
upon by the Module until a valid configuration is received. The
configuration file has the following format.
Output word 0: defines the user's configuration; that is, what types of
inputs are present.
bit 0 when a CW limit switch is used
bit 1 set when a CCW limit switch is used
bit 2 set when the pulse train enable/disable input is used
bit 3 set when an external interrupt is used
bit 4 set when a home limit switch input is used
bit 5 set when a home limit proximity limit switch is used
bits 6 and 7 not used
bit 8 set when a quadrature encoder is used
bit 9 set when diagnostics feedback is used
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
OUTPUT
WORD 0
OUTPUT
WORD 1
OUTPUT
WORD 2
OUTPUT
WORD 3
IMPORTANT
To guard against a configuration error, certain bits in
output word 0 must be set. Either bit 0 or bit 1 (or
both) must be set; and either bit 4 or bit 4 and bit 5
must be set. This is true whether or not the indicated
limit switch is present in the system. Also, there are
certain output combinations that obviously are not
valid (e.g., setting both bit 8 and bit 9). Using an
invalid output combination results in a configuration
error being generated.
Vista de página 38
1 2 ... 34 35 36 37 38 39 40 41 42 43 44 ... 81 82

Comentários a estes Manuais

Sem comentários