14 1734 POINT I/O Protected Output Module
Publication 1734-IN056H-EN-P - May 2013
Output Module 1734-OB8E
Channel Output terminal Common terminal Power
Channel 0 0 Common MUST be daisychained
from either a 1734 adapter;
1734-FPD or 1734-EP24DC, or
from a user-supplied auxiliary
terminal block.
The 24V DC power for the
module is supplied by the
internal power bus and
originates from the same
adapter, 1734-FPD or
1734-EP24DC.
Channel 1 1
Channel 2 2
Channel 3 3
Channel 4 4
Channel 5 5
Channel 6 6
Channel 7 7
ATTENTION: Common MUST be daisychained from either a 1734 adapter;
1734-FPD or 1734-EP24DC, or from a user-supplied auxiliary terminal block.
ATTENTION: Do not wire more than 2 conductors on any single terminal.
Out 1
Out 0
Load
1
0
Out 1
Out 0
1
0
Out 3
Out 2
3
2
Out 5Out 4
5
4
Out 7Out 6
7
6
Load
Load
Load
Load
Load
Load
Load
CC