Publication 1734-UM004F-EN-E - December 2012
Calibrate Your Module 49
2. Click Device Parameters to view the parameters.
The EDS editor may ask you if you want to upload the configuration
from the device.
3. From the EDS editor, if it asks you about uploading the configuration
from the device, click Upload; otherwise, proceed to the next step.
4. From the Device Parameters dialog, click Calibration Channel Select to
bring up your channel selections, and select a channel, or select both.
Click Device Parameters to
view the parameters.
Select the desired channel,
or select “Both Channels.”