Guarded Analog Output Modules
(T3480)
PD
-
6026
Mar
-
06
19
Figure
12
. Guarded Analog Output Module Calibration
Potentiometer Locations.
The I/O extender module has jumper posts that allow you to
connect or disconnect the I/O slot field wiring on the I/O
chassis to the printed circuit board plugged into the I
/O
extender. During the calibration steps you will remove any
jumpers installed on these posts in order to connect the
precision load resistors to the analog outputs. Figure
13
shows the jumper posts to which you should connect the
precision resistors for each analog output channel.