Rockwell-automation T3420AF ICS Regent Analog Input Modules Manual do Utilizador Página 26

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 39
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 25
Analog Input Modules
(T3420A, AF)
26
Industrial Control Services
Figure
15
. Analog Input Module Definition.
3) Edit each point:
Position the cursor on a Point definition and choose Edit
from the Module Definition dialog box to define a name
and description for each I/O point. In the Analog Input
Point dialog, enter a tag name (up to 12 characters) and a
description (u
p to 40 characters). The tag names are used
in the application program to represent the value of the
analog input in your control algorithms and interlocks.
Figure
16
. Defining an Analog Input Point.
Programming
Inputs are referenced in the application program through the
tag names defined in the I/O Configuration Editor. The
analog inputs will range in value from 0 to 4095 over the
voltage range configured for the analog input module. Most
Vista de página 25
1 2 ... 21 22 23 24 25 26 27 28 29 30 31 ... 38 39

Comentários a estes Manuais

Sem comentários