8 Startup Command File
43
FTLDResponseInterval
The FTLDResponseInterval key specifies the time interval
during which the FTLD interface checks for data points that
were marked „bad_quality‟ by the FTLD service. The FTLD
service will mark a data point „bad_quality‟ if the data point
links to an incorrect item (data point) in the FactoryTalk
Diagnostics or if the FTLD service was not able to receive a
data point from the FTLD interface because several others
data points were being added to the FactoryTalk Historian
server at that time. The period can be set in milliseconds
(ms). The default is 5000 ms.