6Ć12
6.4.1 Input
P
arameters for the Logical Exclusive OR Instruction
This table lists the inputs for the XOR instruction and the variable type and data
type/range that each input supports.
Parameter
Description V
ariable T
ype Data Type/Range
EN When this input is true, the instruction executes. When this
input is false, the instruction is not executed and ENO is
false.
Connect a Boolean input or output.
In1
In2
Enter two variables or constants on which you want to
perform the logical XOR.
Note: Any constants entered are displayed in hexadecimal.
D simple
D constant
D element of an array
integer (0ĆFFFF)
double integer
(0ĆFFFFFFFF)
6.4.2 Output
P
arameters for the Logical Exclusive OR Instruction
This table lists the outputs for the XOR instruction and the variable type and data
type/range that each output supports.
Parameter
Description V
ariable T
ype Data Type/Range
ENO Use this output as the input to another instruction for easiĆ
ly chaining multiple instructions. This output follows the
state of EN unless an error occurs.
Connect a contact, coil, or Boolean input to
another instruction.
Out This output contains the result of the XOR operation on
In1 and In2.
D simple
D element of an array
integer (0ĆFFFF)
double integer
(0ĆFFFFFFFF)