Publication 2711-UM014G-EN-P - September 2008 199
Terminal Connections Chapter 12
RS-232 (DH-485) Terminal
Connections
This section describes connections for the RS-232 (DH-485) PanelView
terminals including:
RS-232 ports
connecting to a SLC, CompactLogix, or MicroLogix Controller
(point-to-point)
connecting to a MicroLogix Controller through the AIC+ module
connecting a computer
connecting to a DH-485 link
Refer to page 218
for PanelView 300 Micro RS-232 connections.
RS-232 Terminal Ports
RS-232 (DH-485) PanelView terminals with catalog numbers ending in
5 have a single RS-232 communication port. Terminals with catalog
numbers ending in 9 also have an RS-232 printer port.
Use the RS-232 communication port to:
communicate with a single SLC 5/03, 5/04 or 5/05 controller
(Channel 0 port) or MicroLogix 1000, 1200 or 1500 controller
using point-to-point communication
download/upload PanelView applications
Use the RS-232 printer port to:
connect a printer that supports the IBM enhanced character set.
For connection details, see the last section in this chapter.
The RS-232 communication port and the printer port are reversed on
the PanelView 550 touch screen terminals.
RS-232 Printer Port
RS-232 Communication Port
RS-232 Printer Port
RS-232 Communication Port
PanelView 1000 Terminal
PanelView 550 Terminal