12-2 Installation Instructions
Mounting the DL5
You can mount the DL5 in a custom panel or enclosure.
When the DL5 is properly installed, the faceplate of the DL5 provides a
NEMA Type 12/13 and 4 enclosure integrity rating. To mount the DL5:
1. Punch and drill the appropriate mounting holes in the enclosure or panel.
The following page shows the mounting dimensions of the DL5.
2. Remove the four nuts from the mounting studs on the DL5s face plate.
3. Install the display in the panel cutout and tighten the four nuts on the
mounting studs to a torque of 9 lb-in (1.02Nm).
!
ATTENTION: To avoid ground loops and damage to the
equipment, the same power supply must be used for the parallel
port and the power input to the DL5.
!
ATTENTION: DO NOT install the DL5 until all cutouts and
holes are completed. Metal filings may fall into and damage
the DL5.