DriveLogix Controller for PowerFlex 700S Phase I Drives 17
DriveLogix
Controller LEDs
RUN Green Off No task(s) running.
Controller in Program mode.
Green Steady One or more tasks are running.
Controller is in Run mode.
FORCE Amber Off No forces present.
Amber Steady Forces present and enabled.
Amber Flashing Forces present but not enabled.
BATT Red Off Battery will support memory.
Red Steady Battery may not support memory - replace
battery.
I/O Green Off Controller project not downloaded (the
condition after power up).
No I/O or communications configured.
Green Steady Communicating to all devices.
Green Flashing One or more devices are not responding.
Red Flashing No required I/O connections can be made,
controller is in Run mode.
RS 232 Green Off No activity.
Green Flashing Data being received or transmitted.
OK Off No power applied.
Red Flashing Recoverable fault or ?ash programming.
Red Steady Controller faulted.
Clear faults, clear memory, or replace the
controller.
Green Steady Controller OK.
Type Name Color State Description