12 ArmorBlock MaXum 12 Input/ 4 Output Module Series B
Publication 1792D-IN004B-EN-P - August 2000
Specifications
12 Input / 4 Output Module - Cat. No. 1792D-12BVT4D
Input Specifications Max. Min.
Inputs per block 12 - 3 wire or dry contact PNP or NPN devices or 6 -
4 wire PNP or NPN devices
Sensor Source Current (per input) See the graph below.
Off-Wire Sense Current 0.5mA -
On-state Voltage 25V dc 10V dc
On-state Current 10mA 2mA
Off-state Voltage 5V dc -
Off-state Current - 1.5mA
Output Specifications Max. Min.
Outputs per block 4 sourcing outputs labeled O0 through O3
Off Peak Blocking Voltage 30V 10V
On-state Voltage Drop 1V -
On-state Current 2.0A -
Off-state Leakage 1.5mA -
Module Current (all outputs) 4.0A -
Surge Current - for 10ms,
repeatable every 2s
4.0A -
No Load Sense Current (On-state) 0.18A -
General Specifications
Indicators Net/Mod Status - red/green
Logic Status - red/green
Auxiliary Power - green
Point LED - yellow/orange/red
Communication Rate 125Kbps @ 500 meters(1600 feet) for thick cable,
flat media length 375 meters (1230 feet)
250Kbps @ 200 meters(600 feet) for thick cable,
flat media length 150 meters (492 feet)
500Kbps @ 100 meters (330 feet) for thick cable,
flat media length 75 meters (246 feet)
DeviceNet Power Voltage
Current
Refer to the graphs in the
Overview section of the
ArmorBlock I/O Family Technical
Data, pub. no.
1792-TD001B-EN-P.
25V dc max
175mA max (no sensors)
11V dc min
up to 1.6A (12
sensors @ 50mA per
sensor)
Auxiliary Power Voltage
Current
30V dc max
4A max
10V dc min
4A max
Dimensions (assembled to base)
inches - (Millimeters)
1.9H x 2.7W x 6.85D
(48.26)H x (68.6)W x (174)D (millimeters)