11
Publication 1790-IN011B-EN-P - April 2003
To ensure that the lead values match as closely as
possible:
keep lead resistance as small as possible and less than
25 ohms
use quality cable that has a small tolerance impedance
rating
use a heavy-gauge lead wire which has less resistance
per foot
RTD Wiring Configurations
Three configurations of RTDs can be connected to the
blocks:
2-wire RTD, which is composed of an RTD EXC
(excitation) lead wire and a RTN (return) wire
3-wire RTD, which is composed of a Sense and 2 RTD
lead wires (RTD EXC and RTN)
4-wire RTD, which is composed of a Sense and 2 RTD
lead wires (RTD EXC and RTN). The second sense
wire of a 4-wire RTD is left open.
2-Wire RTD Configuration
CH0_A
CH0_B
COM
Add Jumper
Cable Shield (to Ground)
RTD EXC RTD EXC
Return Return