Installation Instructions
Ethernet-to-DeviceNet Linking Device
Catalog Number 1788-EN2DN
This publication tells you how to install the 1788-EN2DN
Ethernet-to-DeviceNet linking device and use RSNetWorx for DeviceNet
software to configure it.
Topic Page
Important User Information 2
About the Linking Device 6
System Requirements 7
Installing and Configuring the Linking Device 8
Using Diagnostic Web Pages 44
Dimensions 49
DeviceNet Connector Pinouts 50
EtherNet/IP RJ45 Connector Pinouts 50
Specifications 51
Additional Resources 55
Vista de página 0
1 2 3 4 5 6 ... 55 56

Resumo do Conteúdo

Página 1 - Installation Instructions

Installation InstructionsEthernet-to-DeviceNet Linking DeviceCatalog Number 1788-EN2DNThis publication tells you how to install the 1788-EN2DN Etherne

Página 2 - Important User Information

10 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 2011Connect the Linking Device to the DeviceN

Página 3

Ethernet-to-DeviceNet Linking Device 11Rockwell Automation Publication 1788-IN055C-EN-P - September 2011.. 4. Apply power to the linking device an

Página 4

12 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 2011Configure the Linking Device IP AddressSe

Página 5 - Environment and Enclosure

Ethernet-to-DeviceNet Linking Device 13Rockwell Automation Publication 1788-IN055C-EN-P - September 2011The switch represents the binary value of

Página 6 - About the Linking Device

14 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 20111. Click New. You see the Properties dial

Página 7 - System Requirements

Ethernet-to-DeviceNet Linking Device 15Rockwell Automation Publication 1788-IN055C-EN-P - September 2011The following figure shows a flowchart des

Página 8 - Optional Software

16 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 2011Setting the IP Address Using By Using the

Página 9

Ethernet-to-DeviceNet Linking Device 17Rockwell Automation Publication 1788-IN055C-EN-P - September 20114. Leave the password field blank.5. Click

Página 10 - (Blue) CAN Low

18 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 20116. Enter the following values into the IP

Página 11 - 24V DC +

Ethernet-to-DeviceNet Linking Device 19Rockwell Automation Publication 1788-IN055C-EN-P - September 2011(Optional) Register the EDS file in RSNetW

Página 12 - 23456781

2 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 2011Important User InformationSolid-state equi

Página 13

20 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 20114. In the left pane, click DeviceNet, Dev

Página 14

Ethernet-to-DeviceNet Linking Device 21Rockwell Automation Publication 1788-IN055C-EN-P - September 2011Set the DeviceNet MAC ID and Communication

Página 15

22 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 20113. In the left pane, click the + next to

Página 16

Ethernet-to-DeviceNet Linking Device 23Rockwell Automation Publication 1788-IN055C-EN-P - September 20119. Enter the desired MAC address or data r

Página 17 - 5. Click OK

24 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 2011(Optional) Disable AutobaudIf you do not

Página 18

Ethernet-to-DeviceNet Linking Device 25Rockwell Automation Publication 1788-IN055C-EN-P - September 2011 5. Click Execute.In this field SelectObj

Página 19 - (Optional)

26 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 2011You should see a message in the Data rece

Página 20

Ethernet-to-DeviceNet Linking Device 27Rockwell Automation Publication 1788-IN055C-EN-P - September 2011(Optional) Configure DeviceNet I/OI/O Mapp

Página 21

28 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 20111. In RSNetWorx for DeviceNet, go online

Página 22

Ethernet-to-DeviceNet Linking Device 29Rockwell Automation Publication 1788-IN055C-EN-P - September 20118. Select the I/O devices on the left side

Página 23

Ethernet-to-DeviceNet Linking Device 3Rockwell Automation Publication 1788-IN055C-EN-P - September 2011North American Hazardous Location ApprovalT

Página 24 - Disable Autobaud

30 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 201110. Select the Output tab.The Output mapp

Página 25 - IMPORTANT

Ethernet-to-DeviceNet Linking Device 31Rockwell Automation Publication 1788-IN055C-EN-P - September 20113. From the Revision pull-down menu, choos

Página 26

32 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 201114. In the Select Module Type menu, choos

Página 27 - I/O Mapping

Ethernet-to-DeviceNet Linking Device 33Rockwell Automation Publication 1788-IN055C-EN-P - September 2011You see the Module Properties dialog box.1

Página 28

34 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 201122. Click Next. If an RSNetWorx for Devic

Página 29 - 9. Select the Input tab

Ethernet-to-DeviceNet Linking Device 35Rockwell Automation Publication 1788-IN055C-EN-P - September 201124. Write a user program to use the linkin

Página 30 - Optional

36 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 2011Assembly Objects and ConnectionsThree Ass

Página 31

Ethernet-to-DeviceNet Linking Device 37Rockwell Automation Publication 1788-IN055C-EN-P - September 2011Output AssemblyThe output assembly contain

Página 32

38 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 2011Status Assembly Format Byte OffsetSize in

Página 33

Ethernet-to-DeviceNet Linking Device 39Rockwell Automation Publication 1788-IN055C-EN-P - September 201142 1 USINTScrolling Device Address and Sta

Página 34

4 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 2011European Hazardous Location ApprovalThe fo

Página 35

40 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 2011Understanding Status IndicatorsA group of

Página 36 - Size in

Ethernet-to-DeviceNet Linking Device 41Rockwell Automation Publication 1788-IN055C-EN-P - September 2011 Status IndicatorsI/O Status IndicatorTIPI

Página 37

42 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 2011DeviceNet Network Status IndicatorI/O Sta

Página 38 - Status Assembly Format

Ethernet-to-DeviceNet Linking Device 43Rockwell Automation Publication 1788-IN055C-EN-P - September 2011Module Status IndicatorEthernet Link Statu

Página 39

44 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 2011CIP Link Status IndicatorThe CIP Link sta

Página 40

Ethernet-to-DeviceNet Linking Device 45Rockwell Automation Publication 1788-IN055C-EN-P - September 2011Idle NodesThe Idle Nodes page indicates wh

Página 41 - I/O Status Indicator

46 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 2011Node StatusThe Node Status page displays

Página 42 - I/O Status Indicator States

Ethernet-to-DeviceNet Linking Device 47Rockwell Automation Publication 1788-IN055C-EN-P - September 201177 Data size expected by the device does n

Página 43 - Module Status Indicator

48 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 201188 The connection choices (such as polled

Página 44 - Using Diagnostic Web Pages

Ethernet-to-DeviceNet Linking Device 49Rockwell Automation Publication 1788-IN055C-EN-P - September 2011IP ConfigurationThe IP Configuration web p

Página 45 - Invalid Nodes

Ethernet-to-DeviceNet Linking Device 5Rockwell Automation Publication 1788-IN055C-EN-P - September 2011Environment and EnclosureATTENTION: This eq

Página 46 - Node Status

50 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 2011DeviceNet Connector Pinouts EtherNet/IP R

Página 47 - Node Status Codes (cont.)

Ethernet-to-DeviceNet Linking Device 51Rockwell Automation Publication 1788-IN055C-EN-P - September 2011Specifications6RD-7Termination8Termination

Página 48

52 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 2011Wire size DeviceNet connections:See appro

Página 49 - Dimensions

Ethernet-to-DeviceNet Linking Device 53Rockwell Automation Publication 1788-IN055C-EN-P - September 2011Relative humidity• IEC 60068-2-30 (Test Db

Página 50 - DeviceNet Connector Pinouts

54 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 2011Certifications - 1788-EN2DNCertification

Página 51 - Specifications

Ethernet-to-DeviceNet Linking Device 55Rockwell Automation Publication 1788-IN055C-EN-P - September 2011Additional ResourcesThese documents contai

Página 52

Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400Rockwell Automation SupportRockwel

Página 53

6 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 2011About the Linking DeviceThe 1788-EN2DN Eth

Página 54 - Certifications - 1788-EN2DN

Ethernet-to-DeviceNet Linking Device 7Rockwell Automation Publication 1788-IN055C-EN-P - September 2011System RequirementsThe following hardware a

Página 55 - Additional Resources

8 Ethernet-to-DeviceNet Linking Device Rockwell Automation Publication 1788-IN055C-EN-P - September 2011Optional SoftwareRSLogix5000 software, v

Página 56 - Rockwell Automation, Inc

Ethernet-to-DeviceNet Linking Device 9Rockwell Automation Publication 1788-IN055C-EN-P - September 2011Connect the Linking Device to the EtherNet/

Comentários a estes Manuais

Sem comentários