Appendix B
Publication 1771ĆUM127B-EN-P - December 2002
Block Transfer Write and Block
Transfer Read Configurations
for 0 Output/8 Input 1771ĆN
Series Modules
This appendix contains block transfer write and block transfer read
configurations and bit/word descriptions for 1771-N series modules
with no outputs and eight inputs.
Block Transfer Write Configuration Block for 8 Input Modules
Word/Dec. Bit
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word/Octal Bit
17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
0
BTW word type Constant Number of outputs Constant
0
1 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0
1
CJ alarm
enable
Unused = 0
BCD
select
Temp
scale
Verify
2 RTS Sample Time: 1 millisecond units
Channel 1 Programming
3 Low Scale Value
4 High Scale Value
5 Low Alarm Value
6 High Alarm Value
7
Alarm
enable
Rate Alarm: Scaled Units per second
8 Filter Time Constant: 0.1 second units Alarm Deadband
9 Thermocouple Type 0 RTD Type 10 Ohm Offset; 0.01 Ohm units
Channel 2 Programming
10 Low Scale Value
11 High Scale Value
12 Low Alarm Value
13 High Alarm Value
14
Alarm
enable
Rate Alarm: Scaled Units per second
15 Filter Time Constant: 0.1 second units Alarm Deadband
16 Thermocouple Type 0 RTD Type 10 Ohm Offset; 0.01 Ohm units
Channel 3 Programming
17 Low Scale Value
18 High Scale Value