Vista de página 11
Thermocouple/Millivolt Input Module12
Publication 1771Ć5.49 - October 1996
Backplane Power 850mA @ 5V;
Power Dissipation 4.25 Watts maximum
Thermal Dissipation 14.5 BTU/hr
Environmental Conditions
Operating Temperature:
Rate of Change:
Storage Temperature:
Relative Humidity:
0to60
o
C (32 to 140
o
F)
Ambient changes greater than 0.5
o
C per minute may temporarily
degrade performance during periods of change
-40 to 85
o
C (-40 to 185
o
F)
5 to 95% (without condensation)
Field Wiring Arm Cat. No. 1771-WI
Keying Between 20 and 22
Between 24 and 26
Agency Certification
(when product or packaging is
marked)
CSA certified
CSA Class I, Division 2, Groups A, B, C, D certified
UL listed
CE marked for all applicable directives
User Manual Publication 1771Ć6.5.77
The accuracy of your thermocouple readings depends on:
module accuracy
lead resistance effect
accuracy of the thermocouple
Use the calibration procedure in Chapter 7 to adjust your module to
compensate for your specific environment.
Thermocouple Range Accuracy Based on Temperatures
Above 0
o
C
Column A Column B
Thermocouple
Type
Temperature
Range
o
C
Max Error @
Calibration
Temperature (25
o
C)
1
Temperature Drift
o
C/
o
C (0-60
o
C)
or
o
F/
o
F (32-140
o
F)
E -270 to 1000 +0.74
o
C/+1.08
o
F +0.0400
J -210 to 1200 +0.78
o
C/+1.10
o
F +0.0423
K -270 to 1380 +0.77
o
C/+1.15
o
F +0.0640
T -270 to 400 +0.77
o
C/+1.17
o
F +0.0183
R -50 to 1770 +1.50
o
C/+2.11
o
F +0.0914
S -50 to 1770 +1.50
o
C/+2.31
o
F +0.0926
1
Error is specified from 0
o
C (32
o
F) to the maximum range of the thermocouple. Error
does not include thermocouple error (see appendix F). The error does include cold
junction compensation errors.
Use the calibration procedure
in Chapter 7, Module
Calibration, in your
 
  
(publication 1771Ć6.5.77) to
adust your module to
compensate for your specific
environment.