4–4 Configuring Your RTD Module
Publication 1771Ć6.5.129 - March 2000
The complete configuration block for the block transfer write to the
module is defined in below.
Configuration Block for RTD Input Module Block
Transfer Write
Dec. Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Octal Bit 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
1 Sample Time
(for RTS)
Data
Format
RTD
Type
Units of
Measure
Single channel in ohms
2 10 ohm resistance @ 25
o
C
3 Channel 1 Bias
4 Channel 2 Bias
5 Channel 3 Bias
6 Channel 4 Bias
7 Channel 5 Bias
8 Channel 6 Bias
9 Channel 1 calibration
10 Channel 2 calibration
11 Channel 3 calibration
12 Channel 4 calibration
13 Channel 5 calibration
14 Channel 6 calibration
15 Auto-calibration request word
Bit/word descriptions of BTW file words 1 (configuration), 2
(resistance value of 10 ohm copper RTDs), 3 through 8 (individual
channel bias values) and 9 through 14 (individual channel calibration
words) are presented below. Enter data into the BTW instruction
after entering the instruction into your ladder diagram.
Bit/Word Definitions for RTD Input Module
Word Bits Description
Word 1 bits 00-05 If any of these bits are set, the corresponding input channel will be
reported in ohms. If RTDs other than 10 ohm copper or 100 ohm
platinum are used you must report those channels in ohms, not
degrees. Data format on a channel displayed in ohms will default to
binary.
bits 06-07 Determines what units of measure the module reports.
Units of measure Bits 07 06
Degrees C 0 0
Degrees F 0 1
Configuring Block for a
Block Transfer Write
Bit/Word Descriptions