CompactLogix Analog Output Module 7
Rockwell Automation Publication 1769-IN089A-EN-P - March 2011
Assembling the Module
The module can be attached to the controller or an adjacent I/O module before
or after mounting. For mounting instructions, see Panel Mounting on page 9, or
DIN Rail Mounting on page 10. To work with a system that is already mounted,
see Replacing a Single Module within a System
on page 10.
The following procedure shows you how to assemble the Compact I/O system.
1. Disconnect power.
2. Check that the bus lever of the module to be installed is in the unlocked
(fully right) position.
3. Use the upper and lower tongue-and-groove slots (1) to secure the
modules together (or to a controller).
4. Move the module back along the tongue-and-groove slots until the bus
connectors (2) line up with each other.
5. Push the bus lever back slightly to clear the positioning tab (3).
Use your fingers or a small screwdriver.