Rockwell-automation 1769-ASCII Compact Module Manual do Utilizador Página 33

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 40
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 32
Compact 1769-ASCII Module 33
Publication
1769-IN068B-EN-P - May 2005
Troubleshoot with Error Codes
Configuration Error Codes
Value (Hex) Meaning
0 No error
200…3FF Hardware error
400…5FF Configuration error
800…DFF Reserved for future use
E00…FFF Bus master detected error
Value
(H
ex)
Meaning Description
Global Module Errors
0 No error The 1769-ASCII module adds no
module-specific errors.
401 Max output array size exceeded The maximum output array size is too
la
rge.
In alternating mode, channel 0 and
channel 1
must have less than 496
transmit characters.
In simultaneous mode, channel 0 and
channel 1
must have less than 496
transmit characters collectively.
402 Max input array size exceeded The maximum input array size is too
la
rge.
In alternating mode, channel 0 and
channel 1
must have less than 496
receive characters.
In simultaneous mode, channel 0 and
channel 1
must have less than 496
receive characters collectively.
Vista de página 32
1 2 ... 28 29 30 31 32 33 34 35 36 37 38 39 40

Comentários a estes Manuais

Sem comentários