Rockwell-automation 1762-OW16 Relay Output Module Manual do Utilizador Página 16

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 20
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 15
16 MicroLogix 1762-OW16 Relay Output Module
Publication 1762-IN009C-EN-P - July 2013
Isolated groups Group 1: Outputs 0…7
Group 2: Outputs 8…15
Output group to backplane isolation Verified by one of the following dielectric tests: 1836V AC for 1 sec.
or 2596V DC for 1 sec.
265V AC working voltage (IEC Class 2 reinforced insulation)
Output group to output group isolation Verified by one of the following dielectric tests: 1836V AC for 1 sec.
or 2596V DC for 1 sec.
265V AC working voltage (basic insulation)
150V AC working voltage (IEC Class 2 reinforced insulation)
Vendor ID code 1
Product type code 7
Product code 121
Relay Contact Ratings
Volts (max.) Continuous
Amps per Point
(max.)
Amperes
(1)
(1)
Surge Suppression – Connecting surge suppressors across your external inductive load will extend the life of the relay
contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication
1770-4.1
.
Voltamperes
Make Break Make Break
240V AC 2.5A 7.5A 0.75A 1800 VA 180 VA
120V AC 15A 1.5A
125V DC 1.0A
0.22A
(2)
(2)
For DC voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by the
applied DC voltage. For example, 28 VA/48V DC = 0.58A. For DC voltage applications less than 14V, the make/break rating
for relay contacts cannot exceed 2A.
28 VA
24V DC 2.0A 1.2A 28 VA
Output Specifications
Attribute Value
Vista de página 15
1 2 ... 11 12 13 14 15 16 17 18 19 20

Comentários a estes Manuais

Sem comentários