12 ControlNet Foundation Fieldbus Linking Device
Publication
1757-IN022B-EN-P - August 2009
Mount on a Panel
Do these steps to install your linking device on a panel.
1. Verify that the placement of the linking device allows for 50 mm
(2 in.) of space on all sides for adequate ventilation and 75 mm
(3 in.) of space on the left side of the module if straight ControlNet
taps are used.
2. Use the following illustrations to mount the linking device to a panel
by using #8 or M4 screws tightened to 1.1…1.8 N•m (10…16 lb•in).
All dimensions are in mm (in.).
43580
DIN Rail Center Line
168
(6.62)
132
147
(5.78)
122
(4.813)
(5.19)
31991C-M