Publication 1756-UM521C-EN-P - July 2004
3-10 SynchLink Module Features
The Communications Format feature is configured on the following screen.
Table 3.5 SynchLink Module Transmit Communications Formats
Transmit Port Communications Format
Transfer Rate (across the fiber optic
cable) for Each Data Type:
1 Axis, 3 Direct Words, 14 Buffered Axis Data - Updated every 500μS
Direct Data - Updated every 50μS
Buffered Data - Updated every 500μS
2 Axis Axis Data - Updated every 250μS
2 Axis, 3 Direct Words Axis Data - Updated every 500μS
Direct Data - Updated every 50μS
2 Direct Words, 18 Buffered Direct Data - Updated every 50μS
Buffered Data - Updated every 250μS
4 Direct Words, 18 Buffered Direct Data - Updated every 50μS
Buffered Data - Updated every 500μS
4 Direct Words, 8 Buffered Direct Data - Updated every 50μS
Buffered Data - Updated every 250μS
Listen Only, No Transmit Data No data updated in this format
No Transmit Data No data updated in this format