GuardPLC Digital Input/Output Module 15
Rockwell Automation Publication 1753-IN003C-EN-P - June 2010
Digital Outputs
Number of outputs 8 (not electrically isolated)
Output voltage range L+ minus 2V
Output current channels 1…3 and 5…7: 0.5 A @ 60 °C (140 °F)
channels 4 and 8: 1 A @60 °C (140 °F), 2 A @ 50 °C (122 °F)
Surge current per channel 1 A for 10 ms @ 1Hz (channels 1…3 and 5…7)
4 A for 10 ms @ 1Hz (channels 4 and 8)
Current load, min 2 mA per channel
Internal voltage drop 2V max @ 2 A
Leakage current (with 0
signal)
1 mA max @ 2V
Total output current 7 A max with exceeding shut down of all outputs with cyclic reconnecting
Response overload Shut down of the concerned output with cyclic reconnecting
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1
.
Technical Specifications – 1753-IB20XOB8 Module