Rockwell-automation 1746-NO8V SLC 500 8-Point Analog Output Module/ Us Manual do Utilizador Página 29

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 28
Publication 1746-UM026A-EN-P - September 2003
Configuring the Module 4-5
d. The “Options” pull-down allows selection of the data format
(bits 4 to 6 of the channel configuration word):
Options:
1746-NO4 Data Format
Engineering Units
Scaled for PID
Proportional Counts
User-defined
e. “Latch Alarms” and “Reset Latched Alarms” check boxes allow
channel configuration word bits 14 and 15 to be configured.
f. The “Fault Options” pull-down allows channel configuration
fault options to be selected (bits 12 and 13 of the channel
configuration word).
Fault Options:
Reset Output
Hold Output
Preset Output
Refer to the remaining sections of this chapter for a full description of
the available configuration selections.
Vista de página 28
1 2 ... 24 25 26 27 28 29 30 31 32 33 34 ... 73 74

Comentários a estes Manuais

Sem comentários