Rockwell-automation 1738-AENTR Armorpoint 2 Port Enet Adapter Manual do Utilizador Página 15

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 24
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 14
ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A 15
Publication
1738-IN028B-EN-E - February 2010
Red Unrecoverable fault has occurred:
- device is bus off.
1. Make sure an I/O module is not
using a MAC ID = 0.
2. Make sure all backplane
modules are communicating at the
proper baud rate.
3. Cycle power to device.
4. If condition persists, replace
device.
Link 1 or Link 2 Activity/Status
Status Description Recommended action
Off No link established. Verify network cabling, and
correct, as needed.
Green Link established at 100 Mbps. None.
Flashing
green
Transmit or receive activity present
at 100 Mbps.
None.
Yellow Link established at 10 Mbps. None.
Flashing
yellow
Transmit or receive activity present
at 10 Mbps.
None.
PointBus Status (Continued)
Status Description Recommended action
Vista de página 14
1 2 ... 10 11 12 13 14 15 16 17 18 19 20 ... 23 24

Comentários a estes Manuais

Sem comentários