Rockwell-automation 1734-IK Encoder/Counter Modules User Manual Manual do Utilizador Página 61

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 68
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 60
Publication 1734-UM006B-EN-P - August 2005
Configure Modules in RSLogix 5000 Software A-7
4. For Filter, select the Frequency from the following, which is the
value you use to filter A/B/Z inputs when you check a
corresponding checkbox.
No Filter
50 kHz
5 kHz
500 Hz
50 Hz (default)
5. Check the checkboxes for the following, which use the value
you selected for Filter.
Filter A
Filter B
Filter Z
6. For Invert, check the checkbox to invert the signal at Z input, if
you selected the following for Type.
Counter
Encoder X1, Encoder X2, or Encoder X4
Period/Rate
7. For Scalar, if you selected Period/Rate, choose one of the
following values.
1
2
4
8
16
32
64
128
If you apply the filter, you scale the filtered Z. The value you
chose for Scalar scales the Z signal for the following
configurations.
Period/Rate
Continuous/Rate
Pulse Generator
Vista de página 60
1 2 ... 56 57 58 59 60 61 62 63 64 65 66 67 68

Comentários a estes Manuais

Sem comentários