12 1734 POINT I/O EtherNet/IP Adapter
Publication 1734-IN042B-EN-P - October 2013
If you set the switches to an invalid number (for example, 000 or a value greater than 254
excluding 888), the adapter checks to see if you enabled DHCP.
DHCP Enabled and Not Enabled
DHCP State Adapter Action
Enabled Asks for an address from a DHCP server. The DHCP server also assigns other
Transport Control Protocol (TCP) parameters.
Not enabled Uses the IP address (along with other TCP configurable parameters) stored in
nonvolatile memory.
WARNING: When you change switch settings while power is on, an electrical
arc can occur. This could cause an explosion in hazardous location
installations.