Rockwell-automation 1336T Function Block Prog. Manual, Series A/B Manual do Utilizador Página 48

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 180
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 47
2–14 System Component Detail
1336 FORCE — 5.9 August 1995
If you are using a PLC, you would create this same link by doing the
following:
1. Set up your block transfer read and write blocks.
2. Create your data table. For this example, your data table would
look like the following:
BTW
Data File
N10:10
0 8F04 8002 8301
0123456789
Write Link
Service
Request
Destination
Node
Source
Node
The 8002 in column 2 specifies that Node 0 of Block ID 2 (the
Set Reset FF function block) is receiving information. The 8301
specifies that Node 3 of Block ID 1 (the LIMIT function block) is
providing the information.
3. Perform a link processing service request.
Vista de página 47
1 2 ... 43 44 45 46 47 48 49 50 51 52 53 ... 179 180

Comentários a estes Manuais

Sem comentários