4-4 Configuring the Scanner or Bridge
To transmit data between the scanner or bridge and the module, you must
add the 1203-EN1 module as a child device of the scanner or bridge.
1. In the Control Organizer pane, right-click on the scanner or bridge
and select New Module (Figure 4.6
). In our example, we right-click
on the 1756-ENBT/B bridge.
Figure 4.6 Right-Clicking on the Scanner
The Select Module Type dialog box (Figure 4.7) appears.
Figure 4.7 Select Module Type Dialog Box
2. Select ETHERNET-MODULE (Figure 4.7) to configure a
1203-EN1, and then click OK.
The Module Properties dialog box (Figure 4.8
) appears.
Adding the Module and Drive to the I/O Configuration