Rockwell-automation 25B PowerFlex 525 Embedded EtherNet/IP Adapter Manual do Utilizador Página 57

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 56
Rockwell Automation Publication 520COM-UM001B-EN-E - March 2013 57
Configuring the I/O Chapter 4
Generic Profile Example of I/O Image
For the example below, all four [EN Data Out x] and all four [EN Data In
x] parameters are used, resulting in an Input Size of “8” and an Output Size
of “6.
5. After setting the information in the drive’s New Module window, click
OK. The Module Properties window appears.
IMPORTANT
The Datalink parameters [EN Data Out x] and [EN Data In x] do not
actually contain data. These are user-configurable parameters that
only contain the parameter number of the parameter whose data will
be made available for write/read in the I/O image. See Using Datalinks
on page 63.
Adapter
Word and I/O
Logic CommandWord 0
ReferenceWord 1
Datalink 1Word 2
Datalink 2Word 3
Datalink 3Word 4
Datalink 4Word 5
Logic StatusWord 2
FeedbackWord 3
Required
Padword
(1)
Word 0
PadwordWord 1
Datalink 1Word 4
Datalink 2Word 5
Datalink 3Word 6
Datalink 4Word 7
Optional
Required
Optional
Output
Image
(Write)
Input
Image
(Read)
(1) Padwords only apply when using the generic profile. Padwords are not used when using the full-featured drive Add-
On-Profile.
Vista de página 56
1 2 ... 52 53 54 55 56 57 58 59 60 61 62 ... 165 166

Comentários a estes Manuais

Sem comentários