2-5
Publication 1771Ć6.5.30 - November 1998
Figure 2.1
LAST STATE Configuration Jumper
Last State Output Level
Configuration Jumpers
MIN
MID
MAX
Front of Circuit Board
HOLD LAST STATE
Table 2.A lists the output ranges and their minimum, maximum, and
middle values.
Table 2.A
Output Last State Configuration Values
Output Range
Selection
Minimum
Value
Middle Value
Maximum
Value
4Ć20mA 4mA 12mA 20mA
0Ć50mA 0mA 25mA 50mA
1Ć5V 1V 3V 5V
0Ć10V 0V 5V 10V
+10V Ć10V 0V +10V
These output conditions are active only if the following conditions
exist:
the module faults
the processor is in the PROGRAM or TEST mode
rack switch 1 is in the reset position