Rockwell-automation 1734-OV2E_4E_8E POINT I/O Protected Sink Output Mo Manual do Utilizador Página 19

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 28
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 18
POINT I/O Protected Sink Output Module 19
Publication
1734-IN585C-EN-E - December 2005
Default Data Map for the 1734-OV2E Output Module
Message size: 1 Byte
Message size: 1 Byte
Default Data Map for the 1734-OV4E Output Module
Message size: 1 Byte
Message size: 1 Byte
76543 2 1 0
Produces
(scanner Rx)
Not used Ch1 Ch0 Channel status
Where: 0 = no error, 1 = error
76543 2 1 0
Consumes
(scanner Tx)
Not used Ch1 Ch0 Channel state
Where: 0 = Off, 1 = On
76543 2 1 0
Produces
(scanner Rx)
Not used Ch3 Ch2 Ch1 Ch0 Channel
status
Where: 0 = no error, 1 = error
76543 2 1 0
Consumes
(scanner Tx)
Not used Ch3 Ch2 Ch1 Ch0 Channel
state
Where: 0 = Off, 1 = On
Vista de página 18
1 2 ... 14 15 16 17 18 19 20 21 22 23 24 ... 27 28

Comentários a estes Manuais

Sem comentários